News Release from: Spirax Sarco | Subject: Slow opening valve
Edited by the Processingtalk Editorial
Team on 15 August 2003
Slow opening valve brings fast savings
An automatic slow opening valve from Spirax Sarco has helped textile dyer Bulmer and Lumb to halve the cost of the steam it uses for processing and space heating at its Bradford site
An automatic slow opening valve from Spirax Sarco has helped textile dyer Bulmer and Lumb to halve the cost of the steam it uses for processing and space heating at its Bradford site The GBP 6,500 valve installation has paid for itself in just a few weeks
This article was originally published on Processingtalk on 30 Jan 2003 at 8.00am (UK)
Related stories
New integrated flowmeter for steam applications
Spirax Sarco has launched Diva, the first spring-loaded variable area flowmeter to integrate a flow sensing device, temperature sensor, connection accessories and flow computer into a compact unit
Steam trap replacement saves chemical plant GBP50k
A Spirax Sarco survey of the steam system at Great Lakes Chemicals at Trafford Park in Manchester have led to substantial energy savings and improvements in maintenance procedures
Fitted on the output from the two site boilers, rated at 16,000 kg/hr and 4,500 kg/hr and supplying steam at 10 bar g, the valve automatically closes off the steam supply at weekends and overnight.
This simple measure is saving the company thousands of pounds per month.
"Since the valve was installed in November 2002, we have halved the boiler gas consumption by shutting off the steam supply at weekends and during holidays," says Mr Darrell McNulty, Maintenance Manager at Bulmer and Lumb.
"In April we went further and set the valve to close at midnight and re-open at 5am, an hour before production starts".
Previously, the steam lines into the factory were kept open to allow steam at reduced pressure to keep the factory warm and prevent freezing during cold spells, even when production was closed.
Now, when the temperature falls below 2C, an externally mounted thermostatic control opens the new valve a small amount to provide frost protection.
The installation comprises a 200mm electrically actuated valve linked to a pulsed output timer to control the rate of opening.
Slow opening ensures that the steam system is gently warmed and prevents waterhammer, a potential concern for Mr McNulty.
"Some of our engineers thought the build up of water in the pipes during the shut-off period would result in waterhammer when the valve opened.
But this has never happened thanks to the slow opening ability of the valve".