Verwer details fieldbus uses and benefits
Verwer Training and Consultancy has released an introduction to fieldbus, detailing its uses, features and benefits for manufacturers.
The sensors and actuators that are connected to the inputs and outputs (IO) of a programmable controller or PLC (programmable logic controller) are normally mounted in the plant or factory.
Therefore, the IO connections of a traditional control system often involve long runs of cable from the control room to the plant.
To attempt to reduce cabling effort, multi-core cables can be used, but these require junction boxes and/or marshalling racks to route the signals to the correct location.
Consequently, each IO channel can involve many connections as the signal passes from cable to cable.
Such wiring is expensive to install, complex to maintain and fault-finding can be difficult.
Fieldbus is an industrial network that is specifically designed for communication between PLCs or industrial controllers and the field-mounted sensors and actuators.
Fieldbus is designed to replace the point-to-point wiring that connects each sensor and actuator to the controller IO.
When the fieldbus is integrated into the sensor or actuator, the devices often provide additional capability such as remote device configuration and/or testing over the bus.
Integrated devices can also provide diagnostic information back to the control room to help diagnose and locate device faults.
Thus devices with integrated fieldbus are often more capable or 'intelligent' than traditional actuators or sensors.
Remote IO stations can also be used with fieldbus wiring.
Here, the digital or analogue IO modules are mounted in the field, close to the sensors and actuators and the data is communicated to the remote IO module via the fieldbus cable.
However, when using remote IO, the field devices cannot use the bus to communicate additional data such as parameters or diagnostics.
Here, we must use traditional (non-intelligent) actuators and sensors.
Fieldbus has many advantages over conventional point-to-point wiring.
A significant reduction in installation costs (typically 20-40 per cent savings) can be made.
This saving comes from reduced wiring, connections, junction boxes, marshalling cabinets, cable trays and supports.
System expansion and modification is simpler and less expensive since only the additional cable run from the existing network to the new device must be installed.
Two-way communication means that additional information such as calibration and configuration data, diagnostic and test information, and device documentation can be communicated over the network.
Equipment maintenance and servicing become more centralised.
Since communication is digital, accuracy is not affected by noise, interference or electrical loading effects, and so on.
This is a particular advantage in transmitting analogue values.
Open standards mean that multi-vendor systems can be constructed.
Product certification ensures that communication will work between devices from different manufacturers.
There are many different fieldbus types available, most of which are defined by international standards and are supported by many different manufacturers.
Specific fieldbus types are often designed for particular application areas or industries.
For example, the requirements for the process industry are often quite different from those of part manufacturing or materials handling.
What is suitable and cost-effective for one application area is often not appropriate for another.
Sometimes we need a simple low-cost fieldbus; other times we need extensive or flexible data capability.
Some fieldbus systems need to be able to operate in potentially explosive atmospheres; others require extremely high reliability for safety-critical applications.
Some fieldbus systems are designed to carry power to the field devices over the bus cable (power over the bus).
This is often done using just two cable cores to carry power and data.
The different types of fieldbus are generally not compatible with each other.
This means that devices on a network must all use the same type of fieldbus.
However, this does not mean that different fieldbuses cannot be used together in an application.
Gateways can be used to connect one type of network or fieldbus to another.
These provide conversion from one technology to another and allow data to be passed between networks.
Quite often an application will involve several different types of network arranged in a hierarchical manner.
Many people ask why we cannot just have one type of network for all applications and levels.
The answer is that there are many different requirements for communications in separate areas of the plant and at different levels in the hierarchy.
Many different considerations must be taken into account.
The required communication speed; data size and structure; environmental factors such as explosion risk, wet or dirty conditions, ambient temperature variations, and existence of electrical interference, must all be considered.
Some networking solutions are suitable only for clean and dry environments; others can be used in exposed locations.
Cost, capability and robustness often vary greatly from one fieldbus to another.
By far the most common fieldbus is Profibus, which has solutions available for a range of applications including factory automation, process plant including explosive environments, high-speed motion control, and high-integrity functional safety systems.
Another popular bus technology is Actuator-Sensor Interface (AS-I), which is used in factory automation systems.
AS-I is often used in conjunction with Profibus for connecting simple binary (on-off) sensors and actuators to the Profibus network using a gateway.
Ethernet and wireless networking is normally used at the office and plant level for plant management and organisational information across the whole company.
Fieldbus and industrial Ethernet are used at the mid levels for control of plant units or cells for supervisory control and monitoring.
Different fieldbus technologies are used at the lower sensor/actuator levels.
The gateways provide an interface between the different network technologies and allow control and monitoring signals to pass up and down from one network to another.
All the above is really good news for the plant management, system designer, equipment installer, plant engineer and plant operator.
Unfortunately there is a disadvantage when using high-speed digital communications.
Fieldbus is much more sensitive to layout and wiring problems than traditional systems.
System designers must be aware of the rules for design, layout and the many simple but expensive-to-correct pitfalls.
It is essential that installers and maintenance technicians have a basic level of training covering the correct wiring techniques and basics for device and system testing.
Commissioning and maintenance engineers need to be able to use network test tools such as a modern protocol analyser and high-speed oscilloscope to fault-find and health-check the fieldbus network.
Not what you're looking for? Search the site.
Browse by category
- Plant Instrumentation (6585)
- Process Control and Management (3036)
- Communications and HMI (2978)
- Industrial Ethernet systems (309)
- Hazardous area interfaces, Enclosures (251)
- Fieldbus systems, Fibre-optic systems (419)
- Telemetry, data acquisition + loggers (497)
- Alarms management, annunciators and interlocks (309)
- Chart recorders, indicators and totalisers (66)
- Web interrogation and phone messaging (71)
- Displays and remote terminal units (270)
- Signal conditioners, isolators, modems (81)
- Wireless data transmission (214)
- Test equipment (208)
- Wireless process sensors (281)
- Smart Metering Systems (2)
- Process Plant and Equipment (7472)
- Processing Industry Events and Services (3624)
- News from specific industry sectors (2846)
- Environment, Pollution + Green Power (900)
- Flow Measurement (947)
- Water Industry News (1552)